D8 Hall Effect High Current Sensor 1000A DC Current Sensor

The D8 Series current sensor is a closed loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit, the size 

Featured Products

The D8 Series current sensor is a closed loop device based on the measuring principle of the hall effect,

 with a galvanic isolation between primary and secondary circuit,

 the size of primary doesn't affect test precision, no matter the location of primary in the hole of current sensor.

 It can really measure resolution 1000:1, it uses for precision measurement of DC, AC and pulse current. 

 

(Ta=25 ±5 ,RL=2KΩ,CL=10000PF)

 

Type

D8-1000A

Unit

Rated current(Ipn)

±1000

A

Measure range(Ip)

0-±2000

A

Turns ratio(Np/Ns)

1:5000

T

Measure resister 

with±15V

@±1000Amax,        0(min)30(max)

Ω

@±2000Amax,        0(min)20(max)

Ω

Measure resister 

with±24V

@±1000Amax,        0(min)75(max)

Ω

@±2000Amax,        0(min)15(max)

Ω

Coil resister

43

Ω

Rated output

200

mA

Supply voltage

±15,±18,±24

V

Power Consumption

≤20+IpX(Np/Ns)

mA

Offset current

@Ip=0                     ±0.2

mA

Offset drift

@ -40~+85              ≤±0.25

mA

Linearity 

@Ip=0-±Ipn                 ≤0.1

%FS

Response time

@50A/μS, 10%-90%         ≤1

μS

Galvanic isolation

@ 50HZ,AC,1min              6

KV

di/dt

>100

A/us

Bandwidth

@ -1dB                    0~150

KHZ

 

Applications

 

·Variable speed drives

·Welding machine

·Battery supplied applications·Uninterruptible Power Supplies (UPS)

·Electrochemical

 

 Mechanical dimension (for reference only) 

D8 Hall Effect High Current Transducer 1000A DC Current Transducer
 

 

 

Remarks:

1. All dimensions are in mm.

2. General tolerance ±1mm

3. Elucidation:  1:+15V  2:-15V  3:I0UT

 

Directions for use

 

1.When the current will be measured goes through a sensor, the current will be measured at the output end.  (Note: The false wiring may result in the damage of the sensor)

2.Custom design in the different rated input current and the output current are available.

 

Standards

 

·UL94-V0.

·EN60947-1:2004

·IEC60950-1:2001

·EN50178:1998

·SJ 20790-2000

 

General date

 

 

Value

Unit

Operating temperature (TA)

-40 to +85

 

Storage temperature (TS)

-40 to +125

 

Mass(approx) (M)

       550

g

 

 

 

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours